基于闪电定位资料的宣城市雷电绕击率分析与区划
2020-06-24何桂霞田青苏雷
何桂霞 田青 苏雷



摘 要:采用宣城市2010—2018年ADTD型闪电定位系统监测的闪电资料,经质量控制后,利用Excel、VBA编制小程序统计小于1类、2类、3类防雷建筑物滚球半径对应的雷电流幅值概率,结果表明,宣城市建筑物按照规范1类、2类、3类防雷类别设计时,其绕击率分别为0.02%、0.44%、5.94%。因此,针对不同防雷类别,可利用plot函数绘制雷电绕击率区划分布图,以期为防雷减灾工作提供科学依据。
关键词:雷电;绕击率;区划;plot函数
中图分类号 TU976.55文献标识码 A文章编号 1007-7731(2020)11-0158-03
Analysis and Division of Lightning Strike Rate in Xuancheng City Based on Lightning Location Data
He Guixia et al.
(Xuancheng City Meteorological Bureau, Xuancheng 242000, China)
Abstract: Using Xuancheng city from 2010 to 2018, ADTD lightning lightning positioning system monitoring data, after quality control, using Excel and VBA to compile a small program to calculate the probability of lightning current amplitude corresponding to the rolling radius of type 1, type 2 and type 3 lightning protection buildings, it is concluded that when the buildings in Xuancheng are designed according to the type 1, type 2 and type 3 of the code, the around rate is respectively 0.02%, 0.44% and 5.94%. According to different types of lightning protection, Plot function is used to plot the partition distribution of the shielding failure rate due to lightning stroke, It provides scientific basis for lightning protection and disaster reduction.
Key words: Thunder and lightning; Around the rate;Zoning; Plot function
雷电灾害被联合国有关组织列为“最严重的10种自然灾害之一”。在中外历史记载中,雷击造成火灾、建筑物坍塌和人畜伤亡的记录不计其数[1-2]。宣城市隶属南北气候过渡带,境内襟山带水,地形呈南高北低,特殊的气候、复杂的地形,导致境内雷电活动频繁,雷电灾害时有发生[3]。在雷电灾害调查中发现,有的建筑物虽然安装了有效的直击雷防护措施,由于雷电绕击,在LPZ0B区(直击雷防护区)仍然会发生雷电灾害,如2014年9月2日宣城市医药有限公司门卫室屋面遭受雷击,该建筑物处于直击雷保护范围。因此,进行雷电绕击率的分析研究,对于科学有效地防雷具有十分重要的现实意义。
1 资料来源与统计方法
1.1 资料来源 闪电资料来源于安徽省ADTD闪电监测系统,在合肥、蚌埠、阜阳、六安、安庆、宣城、黄山共布设了7套ADTD型闪电探测仪,组成闪电监测网(图1),并于2010年开始投入业务使用。ADTD型闪电监测系统的探测范围广、精度高,探测仪探测半径为100km,地闪位置在系统有效覆盖区域内误差小于1km。……