APP下载

10 kV防爆高压变频器在主煤流系统上的应用

2020-05-19许随利秦志强

河南科技 2020年7期
关键词:节能

许随利 秦志强

摘 要:为解决赵固二矿西胶带大巷带式输送机启动时电流和启动力矩大、驱动电机损坏较为频繁的难题,改造使用BPBJV-1600/10型10 kV防爆高压变频器。本文介绍了10 kV防爆高压变频器在主煤流输送系统中的应用方案、调速控制策略及运行数据分析。实践证明,改造后的系统实现了设备平稳启停,降低了设备故障率,减少了电能消耗,提高了系统运行可靠性。

关键词:防爆高压变频器;功率平衡;软启停控制;节能

中图分类号:TD528.3文献标识码:A文章编号:1003-5168(2020)07-0076-03

Abstract: A 10 kV explosion-proof high-voltage inverter of model BPBJV-1600/10 had been applied to the belt conveyor of the West Belt Road of Zhaogu No.2 Coal Mine to solve the problems of large starting current and torque and frequent damage to the drive motor when the conveyor starts. The application scheme, speed control strategy and operation data analysis of the explosion-proof high-voltage inverter in the main coal flow transmission system were introduced. It has been proved by practice that the reformed system can realize the smooth start and stop of the equipment, reduce the failure rate of the equipment, reduce the power consumption and improve the operation reliability of the system.

Keywords: explosion-proof high-voltage inverter;power balance;soft start and stop control; energy saving

趙固二矿西胶带大巷带式输送机主要负责矿井西部采掘工作面的原煤运输工作,带式输送机型号为DTL140/300/3×710,带宽1 400 mm,运输能力3 000 t/h,带速4 m/s,巷道坡度4.7°~16°,软启动方式为10 kV高压磁力起动器配合恒充式液力耦合器。采用该启动器的原因是使用液力耦合器启动时电流过大,启动力矩大,损坏电机较为频繁。14030一次采全高工作面投产后,西胶带负荷增大,系统运行不确定性因素增加,无法保证生产性。

为解决上述难题,赵固二矿于2019年5月开始对西胶带大巷带上输送机供电系统、驱动部分进行改造,投运10 kV防爆高压变频器,实现了设备平稳启停,降低了设备故障率,节约了电能消耗,提高了系统运行可靠性[1]。

1 西胶带变频改造技术方案

1.1 现场工况介绍

赵固二矿西胶带大巷输送机原系统由3台710 kW/10 kV电机拖动,原电机调速设备为软启动器系列。由于在运行过程中使用软启动时启动电流过大,损坏电机较为频繁,为确保生产稳定性,考虑改用变频控制方案。……