【Abstract】With the improvement of the automation degree of nuclear power plants,DCS has become more and more widely used in nuclear power plants,and the PCB in DCS can be damaged by external strong electricity or inductive power.This paper introduces the process analysis and the causes of the burning of DCS cage mold by electric distribution panel during the commissioning of a nuclear power plant. The method and idea of this kind of analysis are helpful to solve the interference problem of DCS.
【Key words】Nuclear power plant;Electric switchboard;Induction;DCS;IO module
0 引言
某核電厂是我国在翻版加改进的基础上自主设计、建造的百万千瓦级压水堆核电厂,采用了德国西门子公司的非安全级Teleperm-XP和安全级Teleperm-XS全数字化DCS仪控系统。在调试过程中,发生了DCS控制柜机笼模件烧毁的事件。经调查分析,确认了电气配电盘产生感应电是模件烧毁的根本原因。设备厂商对电气配电盘现场改造后彻底消除了感应电的产生,排除了DCS系统安全运行的一个隐患。
1 事件概述
2010-11-18 15点37分某核电厂2号机主控室监视画面突发烟雾探测报警,同时操纵员接到现场工作人员报警电话,报告4LX厂房房间4KCP561AR控制柜冒出烟雾且伴有火花。经现场检查4KCP561AR机柜,发现6个机笼电源分配保险熔断,CA层IO模件工作指示灯全部处于报警状态,柜内CA层机笼模件有烧焦痕迹,电路板焊锡融化,如图1。
随后仪控专业牵头、电气和工艺系统专业配合的调查小组对事件原因进行调查分析。
2 原因查找
西门子Teleperm-XP(T2000)DCS系统包括控制柜、端子柜与电源柜等,每台控制柜主要由CPU、IO模件及附属元件组成,机笼背板是机柜总线的一部分,负责CPU与IO模件的通讯,并给IO模件分配工作电源。……