110 kV交联电缆线芯进水处理

2017-07-10孙进焦爱军时振堂潘玉

当代化工 2017年7期
关键词:故障

孙进 焦爱军 时振堂 潘玉

摘 要: 以110 kV交联电缆进水故障为例,总结了目前电缆在运行管理中出现进水故障的原因、危害和常见处理方法。某石化企业110 kV交联电缆发生单相接地故障后,故障电缆线芯全段进水,无法正常恢复,通过分析电缆故障时线芯负压吸入蒸汽而凝结成水的机理,根据抽真空充氮气的方法制定干燥处理方案,成功地应用抽真空充氮法进行了水分清除,完成电缆修复,为此类电缆进水受潮故障的处理提供参考。

关 键 词:交联电缆;单相接地;进水

中图分类号:TM757 文献标识码: A 文章编号: 1671-0460(2017)07-1450-03

Treatment of Water Infiltration Fault of 110 kV XLPE Power Cable Conductor

SUN Jin1,JIAO Ai-jun2,SHI Zhen-tang1,PAN Yu2

(1. Sinopec Dalian Research Institute of Petroleum and Petrochemcals , Liaoning Dalian 116049, China;

2. Sinopec Qilu Petrochemical Company, Shandong Zibo 255411, China)

Abstract: Taking water infiltration accident of 110 kV XLPE cable as an example, fault reasons, harm and common treatment methods in the cable operation and management were summarized. After the single-phase grounding fault of 110 kV XLPE cable happened in a company, water infiltrated into the whole fault cable conductor, and normal operation was not restored. By analyzing the mechanism of fault cable inhaling the vapor to condense into water, the drying treatment scheme was formulated based on vacuumizing and filling nitrogen method, the moisture was successfully removed and the fault cable was repaired.

Key words: XLPE power cable; Single-phase grounding; Flooding

電力电缆是电力系统输变电线路的主要形式之一,由于其具有绝缘性优异、传输容量比大、满足防爆要求等特点,在石化企业得到了广泛应用,是炼化企业和油田电网输配电网络的重要组成部分[1]。

目前应用广泛的交联聚乙烯有多种敷设方式,包括直埋敷设、隧道敷设和沟道敷设等,应根据工程条件和环境特点,结合可靠性原则和经济性原则选择适合的安装方式。为保证电缆线路的安全可靠,需严格规范电缆本体及附件的产品质量,按照GB50168-92电缆线路施工及验收规范标准规范的具体要求进行敷设安装。在电缆运行过程中出现进水受潮故障后,若不采取措施进行去潮干燥处理,主绝缘结构在水分和高压电磁场的作用下逐步形成水树枝,破坏主绝缘,长时间发展将导致绝缘击穿故障,影响电网稳定和供电安全,甚至导致全厂停电,造成重大经济损失和人员伤害 [2,3]。……