500kV架空输电线路杆塔接地电阻整治技术
2017-07-08张亮沈国欣
张亮 沈国欣
【摘 要】温州地区属于雷电灾害多发地区,温州地区管辖110~500kV线路,由雷击引起线路故障跳闸数约占线路每年故障总数的50%以上,对整个电网的安全运行与供电可靠性造成极大的影响。温州供电公司坚持“安全第一、预防为主、团结协作、科学应对”的方针,以提高输电线路防雷性能为首要任务,科学合理地开展线路防雷改造工作,包括对线路接地排查和整治,最大程度地降低雷电对杆塔的威胁。
【Abstract】Wenzhou area belongs to the lightning disaster prone area, Wenzhou area is under the jurisdiction of 110kV to 500 kV line, line fault tripping caused by lightning strikes accounted for about 50% of the total annual line above the fault, which greatly affect safe operation and reliability of the whole power grid. Wenzhou power company adhere to "safety and prevention first, unity cooperation, scientific response" policy, take improving the lightning protection performance of transmission lines as the primary task, carry out the lightning protection transformation of the line scientifically and rationally, including the line ground investigation and remediation, so as to minimize the threat of lightning to the towers.
【關键词】防雷灾害;整治措施;技术线路
【Keywords】lightning disasters: remediation measures; technical route
【中图分类号】TM726.1 【文献标志码】A 【文章编号】1673-1069(2017)06-0119-02
1 专项改造阶段实施程序
整个专项改造工作分“排查准备、提出方案、验证方案、全面改造”四个阶段,有序推进500千伏线路接地电阻专项改造工作。
1.1 排查准备阶段
2015年6月初,温州供电公司开展500千伏线路接地电阻全面排查工作。在4月15日前完成全市所有500千伏线路接地电阻排查工作。
1.2 提出方案阶段
2015年7月15日前,认真落实各级责任,全面分析500千伏线路接地电阻,提出行之有效的改造方案。
1.2.1 施工方法
①测量原接地电阻值,做好记录。②在距离塔基1m处围着塔基四周挖出4条槽沟(围框大小视塔基根开作实调整),然后再根据地型向两端开挖长20m(根据图纸要求)的槽沟,要求槽沟宽0.5m,深0.8m。③完成槽沟挖好后,在每条开挖好的槽沟内水平放置两根接地线。铺设好的新线尾部必须折弯镶进地下,使其不能翘起。④在两条接地线之间每间隔5m用钢筋连接并用电焊焊牢,其间隔处垂直方向向下打1.5m铁桩,铁桩采用直径20mm的螺纹钢。……