电压切换回路隐患分析及其改进措施
肖硕霜修荣堃党政晋龙兴
(深圳供电局有限公司,广东 深圳518000)
摘要电压切换回路中刀闸辅助接点异常是使得线路或变压器保护不能采到母线电压而误动的主要原因。本文通过分析一起因刀闸常闭辅助接点粘连引起保护误动的事件,总结了现有电压切换回路存在问题,并提出了现有改进方案存在的隐患。本文提出了可避免保护失压的三种方案,并对其中可彻底消除隐患的微机化改造方案设计了具体的实现逻辑。
关键词:电压切换;二次异常并列;辅助接点
Improvement Measure and Analysis of Hidden Danger in Voltage Switching Circuit
Xiao ShuoshuangXiu RongkunDang ZhengJin Longxing
(Shenzhen Power Supply Bureau, Shenzhen, Guangdong518000)
Abstract Protection’s misoperation will be caused when line and transformer protection in normal operation cannot collect the bus voltage. It is one of the main reason that the abnormal auxiliary contact of disconnecting links in voltage switching circuit. This essay summarizes what causes the abnormality in voltage switching circuit by analyzing a case of line protection misoperation because the auxiliary contact is adhesive which is normally closed. For these causes, the hidden danger of improvement project now available has been raised. Then there are three improvement projects can effectively avoid the risk of protection’s voltage-loss has been designed and put forward, one of which can eliminate the danger is microcomputer-based voltage switching circuit and its specific realization logics are designed.
Keywords:voltage switching; abnormal paralleling of secondary circuit; auxiliary contact
继电保护装置的正确动作与母线电压密切相关。双母线接线中,变压器保护和线路保护利用电压切换回路取得其所挂母线的二次电压。当完成倒母线操作后,若电压切换回路中的辅助接点异常或继电器故障,可能使得两条母线的二次电压回路误并列。此时,若两条母线之间存在电压差,PT二次回路中形成的环流使得PT二次空气开关跳闸,造成保护装置不能取到母线电压,引起保护误动。进一步地,若PT二次空开未成功跳闸,将烧毁操作箱插件,误起动失灵保护,使得事故扩大。因此,分析电压切换回路存在的安全隐患并进行改进具有至关重要的意义[1-2]。
1 事故案例简介
2014年05月19日,某220kV变电站的甲线发生AB相间瞬时故障。故障前该站的运行方式,如图1所示。220kV线路故障时,110kV 111PT与112PT二次电压空开跳闸,致使110kV线路保护及主变变中后备保护误动作。……